Process Data Acquisition – PDA

-- Detailed analysis of quality manage&industrial big data sources

高速数采方案

High speed data acquisition scheme

系统

System

Contact us

1 S7-1500 and slave drop data collection scheme

31 Beckhoff Ads

2 S7-400 Ethernet high speed fixed period 2ms

32 EtherCAT

3 S7-300 Ethernet high speed fixed period

33 RS232 / RS485

4 Profinet

34 Rockwell AB PLC

5 S7-400/300/TDC/FM458 Ethernet Variable Access

35 OPC / OPC Ua

6 Standard Ethernet UDP

36 Auxiliary transmission S120

7 Standard Ethernet TCP

37 Main driver system SL150

8 S7 PLC Tools for program debugging - pdaTools

38 B&R - Robot

9 S7-400/300/TDC/FM458 Symbol Variable DB block

39 MITSUBISHI MC protocol - format 4

10 S7-400/300 iso(MAC address)

40 MITSUBISHI MELSECT – QnA 3E

11 S7-300/400 standard ethernet

41 MITSUBISHI Q-Series UDP

12 TDC Ethernet

42 Smart meter DL/T645-2007 protocol

13 S7-1500/1200

43 S7-200 smart

14 MPI/DP variable access

44 Automobile CAN-bus

15 Profibus-DP

45 Alstom HPCi VMIVME 7750 - UDP

16 RFM(Reflective Memory)

46 Collecting KEPServer data through Opc Ua

17 CoDeSys

47 Collecting S7-1500 data through Opc Ua

18 Interface Module

48 Listen to all data on the Profibus bus and collect it

19 Simotion D

49 ABB main drive ACS6000

20 EGD(Ethernet Global Data)

50 Collecting PCI/PCIe card data

21 Modbus Register address

51 Collect TC-net network data

22 Modbus TCP Memory block

52 Collect UDP data forwarded by Tc-net

23 Modbus TCP Register address

53 Collect domestic PLC data

24 FM458 Profibus-DP gateway

54 Other data collection methods

25 GE Fanuc SRTP/ SNPX

55 High speed data forwarding

26 Wago

56 PDA system scheme for converter, RH furnace, LF furnace in steel plant

27 MOOG PLC

57 Continuous Casting Hydraulic Vibration PDA System

28 ABB PLC

58 Hot rolling TDC GDM.PDA system renovation

29 Beckhoff Ethernet

59 USB HID

30 Bechhoff Realtime Ethernet

60 AnyControl

34 Rockwell AB PLC

When the programming environment and authorization are repeatedly installed abnormally, uninstall all installed programs, delete all folders C: Program Files (x86) Common Files Rockwell, C: Program Files (x86) Rockwell Software, C: Users Public Documents Rockwell Automation, and reinstall them. If any service programs are occupied, stop the service first.

34.1 Connect Rockwell PLC with USB

Connect the USB cable (USB2.0 port) from the PLC to the PC, and the driver will be automatically installed.

Opening RSLinx Classic gateway will automatically detect AB_ VBP-1

Right click to install an unknown device driver.

34.2 Set the IP address of the Ethernet communication module

The first method is to use a rotary switch to set the network IP address

Usage conditions:

(1) Module with rotary switch

(2) The target IP address is in the 192.168.1.xxx network segment

Some of Rockwell's Ethernet communication modules come with rotary switches, as shown in the figure below for the 1756 EtherNet/IP communication module. The switch positions vary depending on the module.

When powered on, the module will read the rotary switch data to determine whether the last part of the IP address value is valid. The valid numerical range is 001... 254.

If the set value is valid, the following situations will occur:

IP address=192.168.1.xxx (where xxx represents switch setting)

Subnet Mask=255.255.255.0

Gateway Address=0.0.0.0

In general, it is recommended to set the rotary switch to a valid value before installing the module. However, if the target IP address you want to set is not 192.168.1.xxx, you can use the following method

Set the rotary switch to an invalid value, and then use the second method to set the IP address.

The second method is to use a BOOTP/DHCP server to set the network IP address

Usage conditions:

(1) The module does not have a rotary switch and has BOOTP/DHCP enabled.

(2) The module has a rotary switch but the set value is invalid, and the module has BOOTP/DHCP enabled.

BOOTP/DHCP server is a standalone server used to set IP addresses. You can use a BOOTP/DHCP server to set IP addresses and other Transmission Control Protocol (TCP) parameters.

Access the BOOTP/DHCP server from the following location:

Programs>Rockwell Software>BOOTP DHCP Server

Before starting the BOOTP/DHCP server, ensure that you have obtained the hardware (MAC) address of the module. The hardware address is on the sticker on the side of the communication module, in a format similar to 00-BC-14-55-35.

Specific steps:

(1) Start the BOOTP/DHCP software.

(2) Select Network Settings from the Tools menu.

(3) Enter the subnet mask for the network. The gateway address, primary DNS address and/or secondary DNS address, and domain name fields are all optional items.

(4) Click OK.

The Request History panel will appear, with BOOTP issued

The hardware addresses of all requested modules.

(5) Select the appropriate module.

(6) Click Add to Relationship List. The New Entry dialog box will appear.

(7) Enter the IP address, host name, and module description information.

(8) Click OK.

(9) To permanently assign this configuration to a module, wait for the module to appear in the Relationship List panel and then select it.

(10) Click on Disable BOOTP/DHCP. After cyclic power on, the module will use the assigned configuration without issuing a BOOTP request. If Disable BOOTP/DHCP is not clicked, after cycling power on, the host controller will clear the current IP configuration and issue a BOOTP request again.

The third method: Use RSLinx software or Studio 5000 environment to set the network IP address

The specific steps to set the network IP address using RSLinx software are as follows:

(1) Select RSWho from the Communications menu and the RSWho dialog box will appear.

(2) Connect the PLC using Ethernet.

(3) Right click on the EtherNet/IP module and select Module Configuration. The Module Configuration dialog box will appear.

(4) Click on the Port Configuration tab.

34.3 Connecting Rockwell PLC with Ethernet

PLC cannot be automatically scanned.

Add communication protocol and IP address of PLC.

It is easy to scan to the PLC and update device drivers.

The equipment and communication are both normal.

34.4 Installing RSLinx Classic Gateway Authorization

Run the virtual floppy drive simulation program WinVF.exe, load the authorization impression file gzhstar.img, and run Move Activation -32 Bit to move the relevant authorization from the floppy disk to the hard disk partition.

34.5 Install programming tool RSLogix authorization

34.6 EtherNet/IP

EtherNet/IP (EtherNet Industry Protoco1) is a protocol system suitable for industrial environment applications. It is the latest member launched by two major industrial organizations, ODVA (Open DeviceNet Vendors Association) and ControlNet International. Like DeviceNet and ControlNet, they are networks based on the CIP (Control and Information/on Protoco1) protocol. It is an object-oriented protocol that ensures the effective transmission of implicit real-time I/O information and explicit information (including configuration parameter settings, diagnostics, etc.) on the network.

EtherNet/IP adopts the same application layer CoCIP (Control and Information Protoco1) as DevieNet and ControlNet, therefore they use the same object library and consistent industry standards, with good consistency. EtherNet/IP uses standard EtherNet and TCP/IP technologies to transmit CIP communication packets. In this way, the universal and open application layer protocol CIP, combined with the widely used EtherNet and TCP/IP protocols, constitutes the architecture of the EtherNet/IP protocol.

Rockwell, as a representative, supports ControlLogix CompactLogix MicroLogix and other series.

RSLogix example is follow, one connection may collect most 496 bytes, gather 124 real or 248 int or other type, 124REAL and 120REAL+128BIT are shown below. PDA sample period may be 2ms.

Define User-Defined: TPDA1 as REAL [124]

Define User-Defined: TPDA2 as REAL [120] +SINT [16]

Define two Tags: pda1 and pda2, respective data type is TPDA1 and TPDA2

Establish first connection, fill 10.65.7.216 into Host IP address, and define relevant tag: pda_1, the system automatically produces pda_1: C, pda_1: I, pda_1: O, above figure is shown.

 

Establish second connection, fill 10.65.7.217 into Host IP address, and define relevant tag: pda_2, the system automatically produces pda_2: C, pda_2: I, pda_2:O.

Create user’s program and define cycle period, call this task, fill collect signal into relevant position by serial number.

pda1.AI[0]:=pda1.AI[0]+1;

if pda1.AI[0]>32000 then

   pda1.AI[0]:=-32000;

end_if;

pda1.AI[1]:=sin(pda1.AI[0]*0.03)*1000;

pda1.AI[2]:=cos(pda1.AI[0]*0.05)*1000;

pda1.AI[3]:=1003.0;

......

pda1.AI[122]:=1122.0;

pda1.AI[123]:=1123.0;

COP(pda1.AI[0],pda_1:O.Data[0],496);

 

 

 

pda2.AI[0]:=pda2.AI[0]+1.0;

if pda2.AI[0]>32768.0 then

   pda2.AI[0]:=-32000.0;

end_if;

pda2.AI[1]:=sin(pda2.AI[0]*0.02)*1000.0;

pda2.AI[2]:=cos(pda2.AI[0]*0.02)*1000.0;

pda2.AI[3]:=2003.0;

......

pda2.AI[118]:=2118.0;

pda2.AI[119]:=2119.0;

pda2.DI[0].0:=1;

pda2.DI[0].1:=0;

pda2.DI[0].2:=0;

pda2.DI[0].3:=0;

pda2.DI[0].4:=0;

pda2.DI[0].5:=0;

pda2.DI[0].6:=0;

pda2.DI[0].7:=0;

pda2.DI[1]:=1;

pda2.DI[2]:=2;

pda2.DI[3]:=3;

pda2.DI[4]:=4;

pda2.DI[5]:=5;

pda2.DI[6]:=6;

pda2.DI[7]:=7;

pda2.DI[8]:=8;

pda2.DI[9]:=9;

pda2.DI[10]:=10;

pda2.DI[11]:=11;

pda2.DI[12]:=12;

pda2.DI[13]:=13;

pda2.DI[14]:=14;

pda2.DI[15]:=15;

COP(pda2.AI[0],pda_2:O.Data[0],496);

The PDA server IP address can be set as follows: one network card can receive 2 messages, or multiple physical network cards can be used.

The data source type is 22, Config.csv of PDA server is below, One IP can only collect data from one connection:

[1000,124CH,2.000ms,10.65.7.6,22,EthernetIP,10.65.7.216]

No,    Name,Adr/note,Unit,Len,Offset  ,Gain    ,Type,ALM,HH   ,HI   ,LO   ,LL   ,Opr

CH1=,      ,        ,    ,4  ,0.000000,1.000000,REAL,0  ,0.000,0.000,0.000,0.000,0 

CH2=,      ,        ,    ,4  ,0.000000,1.000000,REAL,0  ,0.000,0.000,0.000,0.000,0 

CH3=,      ,        ,    ,4  ,0.000000,1.000000,REAL,0  ,0.000,0.000,0.000,0.000,0 

……

CH123=,    ,        ,    ,4  ,0.000000,1.000000,REAL,0  ,0.000,0.000,0.000,0.000,0 

CH124=,    ,        ,    ,4  ,0.000000,1.000000,REAL,0  ,0.000,0.000,0.000,0.000,0 

 

[2000,248CH,2.000ms,10.65.7.6,22,EthernetIP,10.65.7.217]

No,    Name,Adr/note,Unit,Len,Offset  ,Gain    ,Type,ALM,HH   ,HI   ,LO   ,LL   ,Opr

CH1=,      ,        ,    ,4  ,0.000000,1.000000,REAL,0  ,0.000,0.000,0.000,0.000,0 

CH2=,      ,        ,    ,4  ,0.000000,1.000000,REAL,0  ,0.000,0.000,0.000,0.000,0 

CH3=,      ,        ,    ,4  ,0.000000,1.000000,REAL,0  ,0.000,0.000,0.000,0.000,0 

……

CH247=,    ,        ,    ,1  ,0.000000,1.000000,BIT ,0  ,0.000,0.000,0.000,0.000,0 

CH248=,    ,        ,    ,1  ,0.000000,1.000000,BIT ,0  ,0.000,0.000,0.000,0.000,0 

Data source type 66 can also collect data in this way, a PDAServer IP can collect data from multiple connections.

Sample period may be 2ms, Recommendatory sample period is more than 10ms, you can reduce data length above if less data point is collected.

You may collect data by standard ethernet if WEB+ module is used, the scheme is not recommended due to complicated PLC’s program.

34.7 EtherNet/IP-backplate

Read the PLC data according to the variable name, no PLC program is needed, the data source type is 29 or 62, and the collection period is not less than 10ms.

The collection program is d:\PDA\pdaCIPClient\pdaCIPClient.exe for 62 data source type, The PDA server side needs to install the VC++2022 runtime library, VC_Redist.x64.exe and VC_Redist.x32.exe.

Supported PLC is Rockwell ControlLogix series.

Global variables of Controller Tags can be collected, the PLC data type are BOOL, SINT, INT, DINT, REAL, STRING. Corresponding PDA data type are BIT, BYT, INT, DINT, REAL, STRING, STRING maximum is 82 characters.

One dimensional array is supported besides STRING.

Below is for configuration example, the ADDRESS column must be same as the variable name in PLC.

[1000,46CH,10.000ms,10.65.7.21,29,Note,10.65.7.216,3]

No,   Name                 ,Adr/note             ,Unit,Len,Offset  ,Gain    ,Type 

CH1=, DiagMinTokHldTime_LSW,DiagMinTokHldTime_LSW,    ,2  ,0.000000,1.000000,INT  

CH2=, DiagTokHldTime_LSW   ,DiagTokHldTime_LSW   ,    ,2  ,0.000000,1.000000,INT  

CH3=, ErrReConfig_ErrMasErr,ErrReConfig_ErrMasErr,    ,2  ,0.000000,1.000000,INT  

CH4=, ErrNotOk             ,ErrNotOk             ,    ,2  ,0.000000,1.000000,INT  

CH5=, abc[0]               ,abc[0]               ,    ,4  ,0.000000,1.000000,DINT 

CH6=, abc[1]               ,abc[1]               ,    ,4  ,0.000000,1.000000,DINT 

CH7=, abc[2]               ,abc[2]               ,    ,4  ,0.000000,1.000000,DINT 

CH8=,                      ,                     ,    ,4  ,0.000000,1.000000,DINT 

CH9=, abc[3]               ,abc[3]               ,    ,4  ,0.000000,1.000000,DINT 

CH10=,abc[4]               ,abc[4]               ,    ,4  ,0.000000,1.000000,DINT 

CH11=,realarray[33]        ,realarray[99]        ,    ,4  ,0.000000,1.000000,REAL 

CH12=,realarray[66]        ,realarray[189]       ,    ,4  ,0.000000,1.000000,REAL 

CH13=,strtest              ,strtest              ,    ,20 ,0.000000,1.000000,STRING

CH14=,abc[5]               ,abc[5]               ,    ,4  ,0.000000,1.000000,DINT 

CH15=,abc[6]               ,abc[6]               ,    ,4  ,0.000000,1.000000,DINT  

CH16=,                     ,                     ,    ,4  ,0.000000,1.000000,DINT 

CH17=,abc[7]               ,abc[7]               ,    ,4  ,0.000000,1.000000,DINT 

CH18=,abc[8]               ,abc[8]               ,    ,4  ,0.000000,1.000000,DINT 

CH19=,abc[800]             ,abc[800]             ,    ,4  ,0.000000,1.000000,DINT 

CH20=,myBool[0]            ,myBool[0]            ,    ,1  ,0.000000,1.000000,BIT  

CH21=,myBool[1]            ,myBool[1]            ,    ,1  ,0.000000,1.000000,BIT  

CH22=,myBool[2]            ,myBool[2]            ,    ,1  ,0.000000,1.000000,BIT  

CH23=,myBool[30]           ,myBool[30]           ,    ,1  ,0.000000,1.000000,BIT  

CH24=,myBool[4]            ,myBool[4]            ,    ,1  ,0.000000,1.000000,BIT  

CH25=,myBool[5]            ,myBool[5]            ,    ,1  ,0.000000,1.000000,BIT  

CH26=,myBool[6]            ,myBool[6]            ,    ,1  ,0.000000,1.000000,BIT  

CH27=,myBool[7]            ,myBool[7]            ,    ,1  ,0.000000,1.000000,BIT  

CH28=,myBool[799]          ,myBool[799]          ,    ,1  ,0.000000,1.000000,BIT  

CH29=,myBool[128]          ,myBool[128]          ,    ,1  ,0.000000,1.000000,BIT  

CH30=,myBool[233]          ,myBool[233]          ,    ,1  ,0.000000,1.000000,BIT  

CH31=,myBool[309]          ,myBool[309]          ,    ,1  ,0.000000,1.000000,BIT  

CH32=,myBool[468]          ,myBool[468]          ,    ,1  ,0.000000,1.000000,BIT  

CH33=,myBool[825]          ,myBool[825]          ,    ,1  ,0.000000,1.000000,BIT  

CH34=,myBool[666]          ,myBool[666]          ,    ,1  ,0.000000,1.000000,BIT  

CH35=,myBool[1000]         ,myBool[1000]         ,    ,1  ,0.000000,1.000000,BIT  

CH36=,sintTest             ,sintTest             ,    ,1  ,0.000000,1.000000,BYTE 

CH37=,sintarray[10]        ,sintarray[10]        ,    ,1  ,0.000000,1.000000,BYTE 

CH38=,sintarray [100]      ,sintarray[100]       ,    ,1  ,0.000000,1.000000,BYTE 

CH39=,                     ,                     ,    ,4  ,0.000000,1.000000,REAL 

CH40=,sintarray[199]       ,sintarray[199]       ,    ,1  ,0.000000,1.000000,BYTE 

CH41=,realtest             ,realtest             ,    ,4  ,0.000000,1.000000,REAL 

CH42=,realarray[50]        ,realarray[50]        ,    ,4  ,0.000000,1.000000,REAL 

CH43=,realarray[99]        ,realarray[99]        ,    ,4  ,0.000000,1.000000,REAL 

CH44=,                     ,                     ,    ,4  ,0.000000,1.000000,REAL 

CH45=,realarray[189]       ,realarray[189]       ,    ,4  ,0.000000,1.000000,REAL 

CH46=,s1                   ,s1                   ,    ,30 ,0.000000,1.000000,STRING

34.8 EtherNet/IP-backplate block

The data source type of 59 or 63.

This method can collect a large amount of data from the PLC at a faster speed. There is no need to program communication in the PLC. The PDA actively reads the data block as a whole, and the supported PLCs are Logix, PLC5, and SLC.

The collection program is d:\PDA\pdaCIPClient\pdaCIPClient.exe for 63 data source type, The PDA server side needs to install the VC++2022 runtime library, VC_Redist.x64.exe and VC_Redist.x32.exe. VC++2022 runtime library and pdaCIPClient.exe do not need to be for type 59, but at most 3990 bytes can be collected.

Define a structure TpdaBlockData in PLC, which gathers the signals to be collected into the variable pdaBlockData of the structure. The length of each data type block of the structure should be an integer multiple of 4 bytes, and the overall COP of pdaBlockData should be copied to the global sint array pdaBlock every scanning cycle. PDA efficiently collects data from pdaBlock, a data access path selected according to the above figure. The data flow is: individual data of various types -> pdaBlockData -> pdaBlock.

The following table is an example of the structure TpdaBlockData.

Name

Data Type

Style

Description

External Access

int16

INT[4]

Decimal

 

Read/Write

int8

SINT[4]

Decimal

 

Read/Write

s1

SINT[20]

Decimal

 

Read/Write

s2

SINT[20]

Decimal

 

Read/Write

s3

SINT[20]

Decimal

 

Read/Write

b1

SINT

Decimal

 

Read/Write

b2

SINT

Decimal

 

Read/Write

b3

SINT

Decimal

 

Read/Write

b4

SINT

Decimal

 

Read/Write

float

REAL[10000]

Float

 

Read/Write

The assignment statement in PLC is as follows.

pdaBlockData.int16[0]:=pdaBlockData.int16[0]+1;

pdaBlockData.int16[1]:=pdaBlockData.int16[0]+10;

pdaBlockData.int16[2]:=pdaBlockData.int16[0]+100;

pdaBlockData.int16[3]:=pdaBlockData.int16[0]+1000;

 

pdaBlockData.int8[0]:=pdaBlockData.int8[0]+1;

pdaBlockData.int8[1]:=pdaBlockData.int8[0]+1;

pdaBlockData.int8[2]:=pdaBlockData.int8[0]+2;

pdaBlockData.int8[3]:=pdaBlockData.int8[0]+3;

 

pdaBlockData.s1[0]:=65;

pdaBlockData.s1[1]:=66;

pdaBlockData.s1[2]:=67;

pdaBlockData.s2[0]:=70;

pdaBlockData.s2[1]:=71;

pdaBlockData.s2[2]:=72;

pdaBlockData.s3[0]:=81;

pdaBlockData.s3[1]:=82;

pdaBlockData.s3[2]:=83;

 

pdaBlockData.b1.0:=1;

pdaBlockData.b1.1:=1;

pdaBlockData.b1.2:=0;

pdaBlockData.b1.3:=1;

pdaBlockData.b1.4:=0;

pdaBlockData.b1.5:=1;

pdaBlockData.b1.6:=1;

pdaBlockData.b1.7:=1;

pdaBlockData.b2:=170;

pdaBlockData.b3:=85;

pdaBlockData.b4:=0;

 

pdaBlockData.float[0]:=pdaBlockData.float[0]+0.01;

pdaBlockData.float[1]:=sin(pdaBlockData.float[0]);

pdaBlockData.float[2]:=cos(pdaBlockData.float[0]);

if pdaBlockData.float[0]>1000.0 then

   pdaBlockData.float[0]:=-1000.0;

end_if;

pdaBlockData.float[1000]:=pdaBlockData.float[1];

cop(pdaBlockData,pdaBlock[0],4088);

The PDA configuration Config.csv is as follows.

[1000,46CH,10.000ms,10.65.7.156,59,Test1,10.65.7.216,,,,,,,1.1]

No,    Name                              ,Adr/note,Unit,Len,Offset  ,Gain    ,Type,

CH1=,  int16                             ,no      ,mm  ,2  ,0.000000,1.000000,INT ,

CH2=,  int16                             ,        ,    ,2  ,0.000000,1.000000,INT ,

CH3=,  int16                             ,        ,    ,2  ,0.000000,1.000000,INT ,

CH4=,  int16                             ,        ,    ,2  ,0.000000,1.000000,INT ,

CH5=,  int8                              ,        ,    ,1  ,0.000000,1.000000,BYTE,

CH6=,  int8                              ,        ,    ,1  ,0.000000,1.000000,BYTE,

CH7=,  int8                              ,        ,    ,1  ,0.000000,1.000000,BYTE,

CH8=,  int8                              ,        ,    ,1  ,0.000000,1.000000,BYTE,

CH9=,  s1                                ,        ,    ,20 ,0.000000,1.000000,CHAR,

CH10=, s2                                ,        ,    ,20 ,0.000000,1.000000,CHAR,

CH11=, s3                                ,        ,    ,20 ,0.000000,1.000000,CHAR,

CH12=, b1.0                              ,        ,    ,1  ,0.000000,1.000000,BIT ,

CH13=, b1.1                              ,        ,    ,1  ,0.000000,1.000000,BIT ,

CH14=, b1.2                              ,        ,    ,1  ,0.000000,1.000000,BIT ,

CH15=, b1.3                              ,        ,    ,1  ,0.000000,1.000000,BIT ,

CH16=, b1.4                              ,        ,    ,1  ,0.000000,1.000000,BIT ,

CH17=, b1.5                              ,        ,    ,1  ,0.000000,1.000000,BIT ,

CH18=, b1.6                              ,        ,    ,1  ,0.000000,1.000000,BIT ,

CH19=, b1.7                              ,        ,    ,1  ,0.000000,1.000000,BIT ,

CH20=, b2.0                              ,        ,    ,1  ,0.000000,1.000000,BIT ,

CH21=, b2.1                              ,        ,    ,1  ,0.000000,1.000000,BIT ,

CH22=, b2.2                              ,        ,    ,1  ,0.000000,1.000000,BIT ,

CH23=, b2.3                              ,        ,    ,1  ,0.000000,1.000000,BIT ,

CH24=, b2.4                              ,        ,    ,1  ,0.000000,1.000000,BIT ,

CH25=, b2.5                              ,        ,    ,1  ,0.000000,1.000000,BIT ,

CH26=, b2.6                              ,        ,    ,1  ,0.000000,1.000000,BIT ,

CH27=, b2.7                              ,        ,    ,1  ,0.000000,1.000000,BIT ,

CH28=, b3.0                              ,        ,    ,1  ,0.000000,1.000000,BIT ,

CH29=, b3.1                              ,        ,    ,1  ,0.000000,1.000000,BIT ,

CH30=, b3.2                              ,        ,    ,1  ,0.000000,1.000000,BIT ,

CH31=, b3.3                              ,        ,    ,1  ,0.000000,1.000000,BIT ,

CH32=, b3.4                              ,        ,    ,1  ,0.000000,1.000000,BIT ,

CH33=, b3.5                              ,not     ,kg  ,1  ,0.000000,1.000000,BIT ,

CH34=, b3.6                              ,        ,    ,1  ,0.000000,1.000000,BIT ,

CH35=, b3.7                              ,note33  ,mol ,1  ,0.000000,1.000000,BIT ,

CH36=, b4.0                              ,        ,    ,1  ,0.000000,1.000000,BIT ,

CH37=, b4.1                              ,        ,    ,1  ,0.000000,1.000000,BIT ,

CH38=, b4.2                              ,        ,    ,1  ,0.000000,1.000000,BIT ,

CH39=, b4.3                              ,        ,    ,1  ,0.000000,1.000000,BIT ,

CH40=, b4.4                              ,        ,    ,1  ,0.000000,1.000000,BIT ,

CH41=, b4.5                              ,not     ,kg  ,1  ,0.000000,1.000000,BIT ,

CH42=, b4.6                              ,        ,    ,1  ,0.000000,1.000000,BIT ,

CH43=, b4.7                              ,note33  ,mol ,1  ,0.000000,1.000000,BIT ,

CH44=, float1                            ,        ,    ,4  ,0.000000,1.000000,REAL,

CH45=, float2                            ,        ,    ,4  ,0.000000,1.000000,REAL,

CH46=, float3                            ,        ,    ,4  ,0.000000,1.000000,REAL,

 

Apparatus test&Fault diagnosis&Quality analysis

Millisecond data sampling

Real-time data compression

Capture signal instantaneous mutation

友情链接 百度 腾讯 新浪 网易 搜狐 凤凰 淘宝 京东 中国自动化网 中国工控网 西门子 罗克韦尔 华军软件园 天空软件站 非凡软件站 多多软件站 携程 知乎

中国五矿 中冶集团 中冶赛迪 中冶南方 中冶京诚 中冶华天 中冶长天 中冶北方 中冶焦耐 中国宝武 宝信 宝钢 武钢 鞍钢 河钢 首钢 山钢 涟钢

ICP2025092850 版权所有©Copyright:2025-2035. 经纬铭月科技(武汉)有限公司

 

 

Develop communication protocol, Customized analysis function, XinChuang domestic obsession

 

PDAServer    PDAClient